Skip to content
Early access — you're among the first to try PYQLabs. Share feedback
Concept drill

Power Systems

GATE Electrical Engineering · Power Systems - Transmission Line Analysis · 1993-2026

56
PYQs
68%
keyed
3
elite explanations
24
years appeared

Study anchor

Source-book anchor pending for this concept.

Practice action

Start latest PYQ

PYQs in this concept

All concepts →
2026 Q18

Consider a power system with N buses, of which P are generator buses and the remaining Q are load buses (where there is no generation). Assume that there are no reactive power-limi...

mediumanswer key
2026 Q19

The initial three-phase voltage phasors ($\bar{V}_A$, $\bar{V}_B$, and $\bar{V}_C$) at a bus of a power network are as shown in Case-1. Due to a disturbance, the bus voltage phasor...

mediumanswer key
2026 Q39

In the circuit shown, the phase currents are $I_A = 572.812+ j50.115 A$ $I_B = -254.525- j459.175 A$ $I_C = -207.083+ j444.091 A$ Given that the CTs are ideal with no saturation, a...

hardanswer key
2026 Q54

For the balanced 3-phase transmission line shown, consider the following cases: Case-1: |V1| = 1.1 p. u., |V2| = 0.9 p. u., Z = 0.75∠0° p. u. and θ12 = θ1 - θ2 = 0° Case-2: |V1| =...

mediumanswer key
2025 Q1

In a power system, following a sudden increase in load, the frequency will settle at a lower steady-state value if

mediumanswer key
2025 Q49

In the system shown below, the generator was initially supplying power to the grid. A temporary LLLG bolted fault occurs at F very close to circuit breaker 1. The circuit breakers...

hardanswer key
2025 PYQ

Two units, rated at 100 MW and 150 MW , are enabled for economic load dispatch. When the overall incremental cost is $10,000 \mathrm{Rs}$./MWh, the units are dispatched to 50 MW an...

mediumbasic explanation
2024 Q34

The incremental cost curves of two generators (Gen A and Gen B) in a plant supplying a common load are shown in the figure. If the incremental cost of supplying the common load is...

medium
2024 Q40

A 3-phase, 11 kV, 10 MVA synchronous generator is connected to an inductive load of power factor (√3/2) via a lossless line with a per-phase inductive reactance of 5 Ω. The per-pha...

hard
2024 Q41

For the three-bus lossless power network shown in the figure, the voltage magnitudes at all the buses are equal to 1 per unit (pu), and the differences of the voltage phase angles...

medium
2024 Q47

Which of the following options is/are correct for the Automatic Generation Control (AGC) and Automatic Voltage Regulator (AVR) installed with synchronous generators?

medium
2023 Q20

For the three-bus power system shown in the figure, the trip signals to the circuit breakers B1 to B9 are provided by overcurrent relays R1 to R9, respectively, some of which have...

medium
2023 Q21

The expressions of fuel cost of two thermal generating units as a function of the respective power generation PG1 and PG2 are given as F1(PG1) = 0.1aP^2_G1 + 40 PG1 + 120 Rs/hour 0...

hard
2023 Q33

A 50 Hz, 275 kV line of length 400 km has the following parameters: Resistance, R = 0.035 Ω/km; Inductance, L = 1 mH/km; Capacitance, C = 0.01 µF/km; The line is represented by the...

hard
2023 Q41

The three-bus power system shown in the figure has one alternator connected to bus 2 which supplies 200 MW and 40 MVAr power. Bus 3 is infinite bus having a voltage of magnitude |V...

medium
2023 Q60

The two-bus power system shown in figure (i) has one alternator supplying a synchronous motor load through a Y-Δ transformer. The positive, negative and zero-sequence diagrams of t...

hard
2023 PYQ

The expressions of fuel cost of two thermal generating units as a function of the respective power generation $${P_{G1}}$$ and $${P_{G2}}$$ are given as $$\matrix{ {{F_1}({P_{G1}})...

mediumanswer keyelite explanation
2022 PYQ

Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6% and 6.4%, respectively, from no load to full load. Both the generating units are operating in...

mediumbasic explanation
2021 PYQ

Two generators have cost functions $F_1$ and $F_2$. Their incremental-cost characteristics are $$ \frac{d F_1}{d P_1}=40+0.2 P_1 \text { and } \frac{d F_2}{d P_2}=32+0.4 P_2 $$ The...

easyanswer keyelite explanation
2021 PYQ

Consider a power system consisting of $N$ number of buses. Buses in this power system are categorized into slack bus. $P V$ buses and $P Q$ buses for load flow study. The number of...

mediumanswer keybasic explanation
2019 Q21

The Ybus matrix of a two-bus power system having two identical parallel lines connected between them in pu is given as Ybus = [-j8 j20] [j20 -j8] The magnitude of the series reacta...

medium
2018 Q9

A source is supplying a load through a 2-phase, 3-wire transmission system as shown in figure below. The instantaneous voltage and current in phase-a are $v_{an} = 220 \sin (100\pi...

mediumanswer key
2018 Q10

A 3-bus power system is shown in the figure below, where the diagonal elements of Y-bus matrix are: $Y_{11} = -j12$ pu, $Y_{22} = -j15$ pu and $Y_{33} = -j7$ pu. The per unit value...

mediumanswer key
2018 Q15

The figure shows the per-phase representation of a phase-shifting transformer connected between buses 1 and 2, where α is a complex number with non-zero real and imaginary parts. F...

hardanswer key
2018 Q29

Consider the two bus power system network with given loads as shown in the figure. All the values shown in the figure are in per unit. The reactive power supplied by generator G1 a...

mediumanswer key
2018 Q30

The per-unit power output of a salient-pole generator which is connected to an infinite bus, is given by the expression, P = 1.4 sin δ + 0.15 sin 2δ, where δ is the load angle. New...

hardanswer key
2018 Q40

The bus admittance matrix for a power system network is $[-j39.9 \quad j20 \quad j20 \\ j20 \quad -j39.9 \quad j20 \text{ pu.} \\ j20 \quad j20 \quad -j39.9]$ There is a transmissi...

hardanswer key
2018 Q51

Consider an overhead transmission line with 3-phase, 50 Hz balanced system with conductors located at the vertices of an equilateral triangle of length Dab = Dbc = Dca = 1m as show...

mediumanswer key
2018 Q52

A 3-phase, 50 Hz generator supplies power of 3MW at 17.32 kV to a balanced 3-phase inductive load through an overhead line. The per phase line resistance and reactance are 0.25$\Om...

hardanswer key
2018 Q53

Two generating units rated 300 MW and 400 MW have governor speed regulation of 6% and 4% respectively from no load to full load. Both the generating units are operating in parallel...

mediumanswer key
2018 PYQ

The positive, negative and zero sequence impedances of a three phase generator are Z 1 , Z 2 and Z 0 respectively. For a line-to-line fault with fault impedance Z f , the fault cur...

mediumanswer key
2017 PYQ

In a load flow problem solved by Newton-Raphson method with polar coordinates, the size of the Jacobian is $$\,100\,\, \times \,\,100.$$ If there are $$20$$ PV buses in addition to...

medium
2015 PYQ

A $$3$$-bus power system network consists of $$3$$ transmission lines. The bus admittance matrix of the uncompensated system is $$\left[ {\matrix{ { - j6} & {j3} & {j4} \cr {j3} &...

mediumanswer key
2015 PYQ

The incremental costs (in rupees/$$MWh$$) of operating two generating units are functions of their respective powers $${P_1}$$ and $${P_2}$$ in $$MW,$$ and are given by $$${{d{C_1}...

medium
2014 PYQ

The fuel cost functions of two power plants are Plant $${P_1}:\,{C_1} = 0.05\,Pg_1^2 + AP{g_1} + B$$ Plant $${P_2}:\,{C_2} = 0.10\,Pg_2^2 + 3AP{g_2} + 2B$$ Where, $$P{g_1}$$ and $$...

mediumanswer key
2014 PYQ

The horizontally placed conductors of a single phase line operating at $$50$$ $$Hz$$ are having outside diameter of $$1.6$$ cm, and the spacing between centers of the conductors is...

mediumanswer keyelite explanation
2012 PYQ

The sequence components of the fault current are as follows: $${{\rm I}_{positive}} = j1.5\,pu,\,\,{{\rm I}_{negative}} = - j0.5\,\,pu,$$ $${{\rm I}_{zero}} = - j1\,\,pu.$$ The typ...

easyanswer key
2012 PYQ

A cylindrical rotor generator delivers $$0.5$$ pu power in the steady-state to an infinite bus through a transmission line of reactance $$0.5$$ pu. The generator no-load voltage is...

hardanswer key
2009 PYQ

For the $${Y_{bus}}$$ matrix of a $$4$$-bus system given in per unit, the buses having shunt elements are $$${Y_{BUS}} = j\left[ {\matrix{ { - 5} & 2 & {2.5} & 0 \cr 2 & { - 10} &...

easyanswer key
2008 PYQ

A lossless power system has to serve a load of $$250$$ $$MW.$$ There are two generators ($$G1$$ and $$G2$$) in the system with cost curves $${C_1}$$ and $${C_2}$$ respectively defi...

mediumanswer key
2008 PYQ

Given that: $$\,{V_{s1}} = {V_{s2}} = 1 + j0\,\,p.u,\,\, + ve\,\,$$ sequence impedance are $$\,{Z_{s1}} = {Z_{s2}} = 0.001 + j0.01\,\,p.u\,\,$$ and $${Z_L} = 0.006 + j\,0.06\,\,p.u...

mediumanswer key
2007 PYQ

Suppose we define a sequence transformation between ''a-b-c'' and ''p-n-0''' variables as follows: $$\left[ {\matrix{ {{f_a}} \cr {{f_b}} \cr {{f_c}} \cr } } \right] = k\left[ {\ma...

mediumanswer key
2004 PYQ

A $$110$$ $$kV,$$ single core coaxial, XLPE insulated power cable delivering power at $$50$$ $$Hz,$$ has a capacitance of $$125$$ $$nF/km.$$ If the dielectric loss tangent of XLPE...

mediumanswer key
2003 PYQ

A list of relays and the power system components protected by the relays are given in List-$${\rm I}$$ and List-$${\rm II}$$ respectively. Choose the correct match from the four ch...

easyanswer key
2003 PYQ

A surge of 20 kV magnitude travels along a lossless cable towards its junction with two identical lossless overhead transmission lines. The inductance and the capacitance of the ca...

mediumanswer key
2001 PYQ

A power system has two generators with the following cost curves Generator $$1:$$ $${C_1}\left( {{P_{G1}}} \right) = 0.006\,P_{G1}^2 + 8{P_{G1}} + 350$$ (Thousand Rupees/Hour) Gene...

medium
2001 PYQ

For the $$Y$$-$$bus$$ matrix given in per unit values, where the first, second, third and fourth row refers to bus $$1, 2, 3$$ and $$4$$ respectively, draw the reactance diagram. $...

medium
2001 PYQ

The conductors of a $$10$$ km long, single phase, two wire line are separated by a distance of $$1.5$$ m. The diameter of each conductor is $$1$$ cm. If the conductors are of coppe...

mediumanswer key
2000 PYQ

The incremental cost characteristic of two generators delivering $$200$$ $$MW$$ are as follows $$\,\,\,{{d{F_1}} \over {d{P_1}}} = 20 + 0.1{P_1},\,\,{{d{F_2}} \over {d{P_2}}} = 16...

easyanswer key
1999 PYQ

An industrial consumer has a daily load pattern of $$2000$$ $$kW$$, $$0.8$$ lag for $$12$$ Hrs. and $$1000$$ $$kW$$ $$UPF$$ for $$12$$ Hrs. The load factor is

easyanswer key
1999 PYQ

An overhead line having a surge impedance of $$400$$$$\Omega $$ is connected in series with an underground cable having a surge impedance of $$100$$$$\Omega $$. If a surge of $$50$...

easyanswer key
1998 PYQ

Each conductor of a $$33$$ $$kV,$$ $$3$$ phase system is suspended by a string of three similar insulators. The ratio of shunt capacitance to mutual capacitance is $$0.1.$$ Calcula...

medium
1996 PYQ

For an unbalanced fault, with paths for zero sequence currents, at the point of fault

mediumanswer key
1995 PYQ

The insulation resistance of a cable of length $$10$$ km is $$1$$ $$M\Omega $$. For a length of $$100$$ km of the same cable, the insulation resistance will be

easyanswer key
1995 PYQ

The positive sequence component of the voltage at the point of fault in a power system is zero for a _________fault.

easy
1993 PYQ

In load flow analysis, the load connected at a bus is represented as

easyanswer key