Skip to content
Early access — you're among the first to try PYQLabs. Share feedback
Concept drill

Fault Analysis

GATE Electrical Engineering · Power Systems - Stability · 1994-2025

23
PYQs
61%
keyed
0
elite explanations
16
years appeared

Study anchor

Source-book anchor pending for this concept.

Practice action

Start latest PYQ

PYQs in this concept

All concepts →
2025 Q49

In the system shown below, the generator was initially supplying power to the grid. A temporary LLLG bolted fault occurs at F very close to circuit breaker 1. The circuit breakers...

hardanswer key
2023 Q60

The two-bus power system shown in figure (i) has one alternator supplying a synchronous motor load through a Y-Δ transformer. The positive, negative and zero-sequence diagrams of t...

hard
2019 Q50

A 30 kV, 50 Hz, 50 MVA generator has the positive, negative, and zero sequence reactances of 0.25 pu, 0.15 pu, and 0.05 pu, respectively. The neutral of the generator is grounded w...

hard
2018 Q28

The positive, negative and zero sequence impedances of a three phase generator are Z₁, Z₂ and Z₀ respectively. For a line-to-line fault with fault impedance Zf, the fault current i...

hardanswer key
2018 PYQ

The positive, negative and zero sequence impedances of a 125 MVA, three-phase, 15.5 kV, star-grounded, 50 Hz generator are 𝑗0.1 pu, j0.05 pu and j0.01 pu respectively on the machi...

medium
2016 PYQ

The magnitude of three-phase fault currents at buses A and B of a power system are 10 pu and 8 pu, respectively. Neglect all resistances in the system and consider the pre-fault sy...

medium
2016 PYQ

A 30 MVA, 3-phase, 50Hz, 13.8 kV, star-connected synchronous generator has positive, negative and zero sequence reactances, 15%, 15% and 5% respectively. A reactance (X n ) is conn...

hard
2015 PYQ

A 50 Hz generating unit has H-constant of 2 MJ/MVA. The machine is initially operating in steady state at synchronous speed, and producing 1 pu of real power. The initial value of...

medium
2014 PYQ

A three phase, $$100$$ $$MVA,$$ $$25$$ $$kV$$ generator has solidly grounded neutral. The positive, negative, and the zero sequence reactance's of the generator are $$0.2$$ $$pu$$,...

medium
2012 PYQ

The sequence components of the fault current are as follows: $${{\rm I}_{positive}} = j1.5\,pu,\,\,{{\rm I}_{negative}} = - j0.5\,\,pu,$$ $${{\rm I}_{zero}} = - j1\,\,pu.$$ The typ...

easyanswer key
2008 PYQ

Given that: $$\,{V_{s1}} = {V_{s2}} = 1 + j0\,\,p.u,\,\, + ve\,\,$$ sequence impedance are $$\,{Z_{s1}} = {Z_{s2}} = 0.001 + j0.01\,\,p.u\,\,$$ and $${Z_L} = 0.006 + j\,0.06\,\,p.u...

hardanswer key
2006 PYQ

A generator feeds power to an infinite bus through a double circuit transmission line. A 3 phase fault occurs at the middle point of one of the lines. The infinite bus voltage is 1...

mediumanswer key
2006 PYQ

For a power system the admittance and impedance matrices for the fault studies are as follows. $$$\eqalign{ & {Y_{bus}} = \left[ {\matrix{ { - j8.75} & {j1.25} & {j2.50} \cr {j1.25...

hardanswer key
2006 PYQ

For a power system the admittance and impedance matrices for the fault studies are as follows. $$$\eqalign{ & {Y_{bus}} = \left[ {\matrix{ { - j8.75} & {j1.25} & {j2.50} \cr {j1.25...

mediumanswer key
2004 PYQ

A 500 MVA, 50 Hz, 3-phase turbo-generator produces power at 22 kV. Generator is Y-connected and its neutral is solidly grounded. Its sequence reactances are X 1 = X 2 = 0.15 and X...

mediumanswer key
2004 PYQ

A 50 Hz, 4-pole, 500 MVA, 22 kV turbo-generator is delivering rated megavolt-amperes at 0.8 power factor. Suddenly a fault occurs reducing is electric power output by 40%. Neglect...

mediumanswer key
2004 PYQ

A $$3$$-phase generator rated at $$110$$ MVA, $$11$$ kV is connected through circuit breakers to a transformer. The generator is having direct axis sub-transient reactance $$X'{'_d...

mediumanswer key
2003 PYQ

A 20-MVA, 6.6-kV, 3-phase alternator is connected to a 3-phase transmission line. The per unit positive sequence, negative sequence and zero sequence impedance of the alternator ar...

hardanswer key
2000 PYQ

The severity of line-to-ground and three phase faults at the terminals of an unloaded synchronous generator is to be same. If the terminal voltage is $$1.0$$ p.u. and $${Z_1} = {Z_...

mediumanswer key
2000 PYQ

A synchronous generator, having a reactance of 0.15 p.u., is connected to an infinite bus through two identical parallel transmission lines having reactance of 0.3 p.u. each. In st...

hard
1997 PYQ

For a fault at the terminals of a synchronous generator, the fault current is maximum for a

easyanswer key
1995 PYQ

The positive sequence component of the voltage at the point of fault in a power system is zero for a _________fault.

easy
1994 PYQ

In a power-system, the $$3$$-phase fault MVA is always higher than the single-line-ground fault MVA at a bus (State True or False)

easyanswer key